A new distributed measurement index for the identification of harmonic distortion and/or unbalance sources based on the IEEE Std. 1459 framework

dc.contributor.authorPérez Vallés, Alejandro
dc.contributor.authorSalmerón Revuelta, Patricio
dc.date.accessioned2025-11-26T12:52:50Z
dc.date.available2025-11-26T12:52:50Z
dc.date.issued2019
dc.descriptionArtículo de investigación en el entorno de la ingeniería de potencia. En concreto aborda el problema de la identificación de cargas eléctricas con carácter no lineal y desequilibrado. Se propone un índice de caracterización de naturaleza distribuida que tenga en cuenta no sólo la carga objetivo sino también la red de distribución.
dc.description.abstractThe number and power of time-varying nonlinear loads connected to the electricity network has increased progressively in recent years, resulting in voltage and current disturbances. In the current, deregulated electricity market, with the proliferating presence of Distributed Generation (DG), it is becoming increasingly important to identify the source of such power quality disturbances. This paper presents a new index based on distributed measurements that allows us to identify the location of sources of harmonic distortion and/or unbalance in distribution networks. The novelty of the proposal lies in the use of terms taken from a different decomposition of apparent power for harmonic distortion and unbalance in power systems under IEEE Std. 1459. From these new terms, a series of indicators have been defined that facilitate the evaluation of the harmonic distortion and voltage unbalance of each user with respect to the electric power supply. The proposed index is validated by means of an experimental platform in which different working conditions have been developed, including load with capacitor banks for power factor compensation.
dc.description.departmentIngeniería Eléctrica y Térmica, de Diseño y Proyectos
dc.identifier.citationPérez Vallés, A., & Salmerón Revuelta, P. (2019). A new distributed measurement index for the identification of harmonic distortion and/or unbalance sources based on the IEEE Std. 1459 framework. Electric Power Systems Research, 172, 96–104. https://doi.org/10.1016/j.epsr.2019.03.007
dc.identifier.doi10.1016/j.epsr.2019.03.007
dc.identifier.urihttps://hdl.handle.net/10272/27445
dc.language.isoeng
dc.publisherElsevier
dc.relation.publisherversionhttps://doi.org/10.1016/j.epsr.2019.03.007
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 International
dc.rights.accessRightsopen access
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.subject.otherPower quality
dc.subject.otherHarmonics
dc.subject.otherUnbalance
dc.subject.otherDistributed measurements
dc.subject.unesco3306 Ingeniería y Tecnología Eléctricas
dc.subject.unesco3306.09 Transmisión y Distribución
dc.titleA new distributed measurement index for the identification of harmonic distortion and/or unbalance sources based on the IEEE Std. 1459 framework
dc.typejournal article
dc.type.hasVersionAM
dspace.entity.typePublication
relation.isAuthorOfPublication18188fe7-402f-425f-9629-7b65026594e8
relation.isAuthorOfPublicationacbb1804-e3c7-463b-aeae-bc51215f04a2
relation.isAuthorOfPublication.latestForDiscovery18188fe7-402f-425f-9629-7b65026594e8